#!/usr/bin/python
# -*- encoding: utf-8; py-indent-offset: 4 -*-
# +------------------------------------------------------------------+
# |             ____ _               _        __  __ _  __           |
# |            / ___| |__   ___  ___| | __   |  \/  | |/ /           |
# |           | |   | '_ \ / _ \/ __| |/ /   | |\/| | ' /            |
# |           | |___| | | |  __/ (__|   <    | |  | | . \            |
# |            \____|_| |_|\___|\___|_|\_\___|_|  |_|_|\_\           |
# |                                                                  |
# | Copyright Mathias Kettner 2014             mk@mathias-kettner.de |
# +------------------------------------------------------------------+
#
# This file is part of Check_MK.
# The official homepage is at http://mathias-kettner.de/check_mk.
#
# check_mk is free software;  you can redistribute it and/or modify it
# under the  terms of the  GNU General Public License  as published by
# the Free Software Foundation in version 2.  check_mk is  distributed
# in the hope that it will be useful, but WITHOUT ANY WARRANTY;  with-
# out even the implied warranty of  MERCHANTABILITY  or  FITNESS FOR A
# PARTICULAR PURPOSE. See the  GNU General Public License for more de-
# tails. You should have  received  a copy of the  GNU  General Public
# License along with GNU Make; see the file  COPYING.  If  not,  write
# to the Free Software Foundation, Inc., 51 Franklin St,  Fifth Floor,
# Boston, MA 02110-1301 USA.


# TODO: This device provides multiple temperature readings, currently
#   only one is evaluated: "Return Air"
#   Right now the items are not named according to the guideline


factory_settings["stulz_temp_default_levels"] = {
    "levels": (25, 28)
}

def inventory_stulz_temp(info):
    for line in info:
        yield line[0], {}

def check_stulz_temp(item, params, info):
    for line in info:
        if line[0] == item:
            return check_temperature(int(line[1])/10, params, "stulz_temp_%s" % item)

check_info["stulz_temp"] = {
    "check_function"         : check_stulz_temp,
    "inventory_function"     : inventory_stulz_temp,
    "service_description"    : "Temperature %s",
    "has_perfdata"           : True,
    "group"                  : "temperature",
    "snmp_scan_function"     : lambda oid: oid(".1.3.6.1.2.1.1.2.0") == ".1.3.6.1.4.1.29462.10",
    "snmp_info"              : ( ".1.3.6.1.4.1.29462.10.2.1.1.1.1.1.1.1.1192", [ OID_END, 1] ),
    "includes"               : [ "temperature.include" ],
    "default_levels_variable": "stulz_temp_default_levels"

}